| Notes |
| Date |
Text |
| 2012-12-19 09:53:05 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | INDICATE THE SIZE AND LOCATION OF THE ELECTRICAL PANEL. | | | ON A FLOOR PLAN SHOW THE LOCATION OF ALL NEW LIGHTING | | | OUTLETS, RECEPTACLE OUTLETS AND SMOKE DETECTORS. NEC | | | 215.5, 210.50 | | | | | | INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER | | | RESISTANT. NEC 406.11 | | | | | | ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE | | | PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC | | | 210.12 | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | | | | |
|