2012-12-19 09:53:05PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 INDICATE THE SIZE AND LOCATION OF THE ELECTRICAL PANEL.
 ON A FLOOR PLAN SHOW THE LOCATION OF ALL NEW LIGHTING
 OUTLETS, RECEPTACLE OUTLETS AND SMOKE DETECTORS. NEC
 215.5, 210.50
  
 INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER
 RESISTANT. NEC 406.11
  
 ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE
 PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC
 210.12
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
  
  