| Plan Review Notes For Permit 12110413 |
| Permit Number |
12110413 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-11-26 09:38:44 | 12110413 | | | 4001 NORTH SHORE DRIVE | | | SITE LIGHTING | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENT. | | | | | | PROVIDE A SIGNED AND SEALED ENGINEERING FOR THE WIND | | | LOAD DESIGN FOR LIGHT POLES AND FIXTURES COMBINED. | | | PROVIDE SOIL AND BURIAL DETAIL FOR THE LIGHT POLES. | | | INDICATE THE EXPOSURE CATEGORY AND IMPORTANCE FACTOR. | | | FBC 2010 1609, ASCE 7-10 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|