2012-11-19 09:04:0212110354
 1023 N. DIXIE HWY.
 SERVICE UPGRADE
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 INDICATE THE FAULT CURRENT CAPABILITY OF THE SERVICE
 EQUIPMENT. NEC 110.9
 PROVIDE WIRE SIZES FOR EACH SERVICE. NEC T. 310.16
 THE SERVICE FEEDER IS UNDERSIZED BASED ON THE LOAD
 CALCULATION SUBMITTED. NEC 310.16
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
 VERIFY THE REQUIRED WORKING CLEARANCES AND DEDICATED
 WORKING SPACE HAS BEEN PROVIDED AT THE ELECTRICAL
 SERVICE. NEC 110.26, 240.24
 VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING
 ARE SIX OR LESS AND GROUPED IN ONE LOCATION.
 NEC 230.2, 230.71, 230.72
  