| Plan Review Notes For Permit 12110354 |
| Permit Number |
12110354 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-11-19 09:04:02 | 12110354 | | | 1023 N. DIXIE HWY. | | | SERVICE UPGRADE | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | INDICATE THE FAULT CURRENT CAPABILITY OF THE SERVICE | | | EQUIPMENT. NEC 110.9 | | | PROVIDE WIRE SIZES FOR EACH SERVICE. NEC T. 310.16 | | | THE SERVICE FEEDER IS UNDERSIZED BASED ON THE LOAD | | | CALCULATION SUBMITTED. NEC 310.16 | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND. NEC 250.94 | | | VERIFY THE REQUIRED WORKING CLEARANCES AND DEDICATED | | | WORKING SPACE HAS BEEN PROVIDED AT THE ELECTRICAL | | | SERVICE. NEC 110.26, 240.24 | | | VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING | | | ARE SIX OR LESS AND GROUPED IN ONE LOCATION. | | | NEC 230.2, 230.71, 230.72 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|