| Plan Review Notes For Permit 12110343 |
| Permit Number |
12110343 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2012-12-18 15:13:04 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. ORIGINAL PERMIT FOR THIS BUILDING WAS FOR A NON | | | COMBUSTIBLE BUILDING, BASED ON THE PLANS PROVIDED FROM | | | 1998. ENGINEER IS NOW CHANGIN THE BUILDING TYPE TO TYPE | | | III, WHICH REQUIRES NON COMBUSTIBLE WALLS BUT ALLOWS | | | COMBUSTIBLE ROOF AND INTERIOR WALLS. | | | | | | IN ORDER TO CHANGE THE BUILDING TYPE TO A TYPE LESS | | | STRINGENT THAN ORIGINALLY CONSTRUCTED, CODE COMPLIANCE | | | FOR THE NEW BUILDING TYPE MUST BE SHOWN. SEE FBC TABLES | | | 601, 602, FBC EXISTING BUIDLING 601.2. | | | | | | IT APPEARS THAT THE SIMPLEST RESOLUTION WOULD BE TO | | | ALLOW THE BUILDING TYPE TO REMAIN NON COMBUSTIBLE (TYPE | | | I OR TYPE II) AND TO REVISE THE WALL DETAILS TO BE FRT | | | OR METAL STUD. | | | | | | |
|