2012-12-18 15:13:04****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. ORIGINAL PERMIT FOR THIS BUILDING WAS FOR A NON
 COMBUSTIBLE BUILDING, BASED ON THE PLANS PROVIDED FROM
 1998. ENGINEER IS NOW CHANGIN THE BUILDING TYPE TO TYPE
 III, WHICH REQUIRES NON COMBUSTIBLE WALLS BUT ALLOWS
 COMBUSTIBLE ROOF AND INTERIOR WALLS.
  
 IN ORDER TO CHANGE THE BUILDING TYPE TO A TYPE LESS
 STRINGENT THAN ORIGINALLY CONSTRUCTED, CODE COMPLIANCE
 FOR THE NEW BUILDING TYPE MUST BE SHOWN. SEE FBC TABLES
 601, 602, FBC EXISTING BUIDLING 601.2.
  
 IT APPEARS THAT THE SIMPLEST RESOLUTION WOULD BE TO
 ALLOW THE BUILDING TYPE TO REMAIN NON COMBUSTIBLE (TYPE
 I OR TYPE II) AND TO REVISE THE WALL DETAILS TO BE FRT
 OR METAL STUD.
  
  