| Plan Review Notes For Permit 12110343 |
| Permit Number |
12110343 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-12-18 07:59:32 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. PLANS SHOW BUILDING AS A TYPE IV. THIS IS HEAVY | | | TIMBER. IT APPEARS THAT ENGINEER USED THE BUILDING TYPE | | | WHICH WAS ON THE PLAN FROM 1998. THE CODE HAS CHANGED A | | | NUMBER OF TIMES SINCE THEN. PLAN STATES THAT, AS A 1998 | | | TYPE IV, THIS IS A NON COMBUSTIBLE BUILDING. | | | | | | PLEASE SEE FBC CHAPTER 6 AND SELECT AN APPROPRIATE | | | BUILDING TYPE. DETAILS FOR THE NEW PARTITIONS SHOW WOOD | | | FRAMING. PLEASE SEE FBC 602.3, TABLE 601, AND 603. | | | | | | ***IT IS POSSIBLE THAT A PERMIT CAN BE ISSUED WITH | | | PROVISO THAT PLANS BE REVISED TO CORRECTLY REFLECT | | | BUILDING TYPE, OR TO OFFICIALLY CHANGE THE BUILDING | | | TYPE, AND NEW DETAILS BE SUBMITTED.*** | | | | | | | | | |
|