| Notes |
| Date |
Text |
| 2012-11-26 09:57:42 | 2658 ELECTRONICS WAY | | | PERMIT #12110343 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE ADDRESS PROVIDED ON THE PLANS (2656) DOES NOT MATCH | | | THE ADDRESS (2658) PROVIDED ON THE PERMIT APPLICATION. | | | | | | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO | | | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION | | | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING | | | SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR | | | AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL | | | HAVE "NO SMOKING" SIGNS POSTED. | | | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE | | | ALARM SYSTEM. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY | | | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING | | | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM | | | WWW.KNOXBOX.COM. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|