| Plan Review Notes For Permit 12110335 |
| Permit Number |
12110335 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-11-20 13:09:33 | FBC 2010 ACCESSIBILITY CODE | | | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | | | | 1. TWO SINKS AND THE WASHING MACHINE THAT ARE SHOWN ON | | | THE PLANS ARE NOT SHOWN ON THE ISOMETRIC DRAWINGS. | | | | | | 2. IF THE OCCUPANCY LOAD IS OVER 15, A HI/LO DRINKING | | | FOUNTAIN WILL BE REQUIRED. | | | FBC PLUMBING 2010 403.1 (E & F) | | | FBC 2010 ACCESSIBILITY 211.2 | | | | | | 3. FRONT CLEARANCE FOR THE WATER CLOSET IS REQUIRED TO | | | BE 56" FROM THE REAR WALL. | | | FBC 2010 ACCESSIBILITY 604.3.1 | | | | | | 4. THE SHOWER DOES NOT MEET THE REQUIREMENTS OF: | | | FBC 2010 ACCESSIBILITY 608.2.1 | | | | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|