| Plan Review Notes For Permit 12110332 |
| Permit Number |
12110332 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-11-30 16:29:21 | 12110332 | | | 250 S AUSTRALIAN AVENUE # 200 | | | COMMERCIAL INTERIOR ( DIGITAL) | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENT. | | | | | | ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH | | | GFCIS. NEC 422.52 | | | | | | VENDING MACHINES SHALL BE PROTECTED WITH GFCIS. NEC | | | 422.51 | | | | | | INDICATE ON THE PLAN THE LOCATION OF THE PANEL BOARDS, | | | TRANSFORMER AND FEEDERS. VERIFY SAFETY CLEARANCES HAVE | | | BEEN OBSERVED. NEC 215.5, 110.26 | | | | | | NOTE: | | | SEPARATE PERMIT ARE REQUIRED FOR VOICE, DATA AND FIRE | | | ALARM. | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|