Plan Review Notes
Plan Review Notes For Permit 12110313
Permit Number 12110313
Review Stop B
Sequence Number 1
Notes
Date Text
2012-11-19 10:55:03****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. AS THERE HAS BEEN A RENTAL LISTING FOR THIS
 PROPERTY, THIS IS INELIGIBLE FOR OWNER/BUILDER FS489.
 HAVE A CONTRACTOR SUBMIT APPLICATION FOR THIS PERMIT
 AND FOR #12030632.
  
 2. PLEASE APPLY FOR AN INSPECTION PERMIT. INSPECTOR IS
 TO DO THE FOLLOWING:
  
 VERIFY INTEGRITY OF SUBSTRATE FOR THE SIDING REPAIR
 INSPECT THE ELECTRICAL SYSTEM TO SEE HOW COMBINING TWO
 UNITS WILL AFFECT REQUIRMENTS SUCH AS SMOKE ALARMS
 DETERMINE WHETHER THE WALL TO BE REMOVED IS A BEARING
 OR NON BEARING WALL
 DETERMINE WHETHER A STRUCTURAL DETAIL IS REQUIRED FOR
 "BUCK REPAIR"
  
 APPLICATION CAN BE MADE BY ANY INDIVIDUAL (DOES NOT
 NEED TO BE A CONTRACTOR AS NO WORK IS AUTHORIZED) USING
 THE SAME PERMIT APPLICATION AND SUBMITTED AT
 CONSTRUCTION SERVICES.
  
 3. PLEASE ADVISE, IS THERE A SECONDARY ADDESS FOR THE
 REAR BUILDING? IT APPEARS THAT THE DRIVEWAY FOR THE
 REAR BUILDING IS ON MERCER; WHERE IS THE FRONT DOOR?
  
 4. PLAN TO SHOW ALL WORK TO BE DONE (NOT ON THE
 APPLICATION AND TYPED SHEET). ALL WORK PROPOSED TO BE
 INCORPORATED INTO THE PLAN.
  
 5. APPLICATION STATES THAT FOUR UNITS WILL BE TURNED
 INTO TWO UNITS. EACH BUILDING REQUIRES A SEPARATE
 PERMIT. PLANS NOT PROVIDED FOR REAR BUILDING. PROVIDE
 AN APPLICATION AND PLANS FOR EACH BUILDING.
  
 A COMPLETE PLAN REVIEW CANNOT BE DONE UNTIL AFTER THE
 PRE INSPECTION IS COMPLETED.
  
  
  
  
  
  