Plan Review Notes
Plan Review Notes For Permit 12110275
Permit Number 12110275
Review Stop M
Sequence Number 1
Notes
Date Text
2012-12-11 15:39:44*** PROVISO ***
 1) 2010 FBC 1503.7, CONDENSATE LINES AND ROOF
 DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT (305 MM)
 AWAY FROM THE STRUCTURE SIDEWALL, WHETHER BY
 UNDERGROUND PIPING, TAIL EXTENSIONS, OR SPLASH BLOCKS.
  
 2) PTAC UNIT NEEDS TO BE A MINIMUM EER OF 12.5, SEE
 2010 FBC/ENERGY TABLE 503.2.3 (3).