2012-11-19 14:23:533401 PARKER AVENUE - PRESS BOX
 PERMIT #12110275
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A NAME, ADDRESS OR LETTER ON THE BUILDING SO
 THE LOCATION CAN BE IDENTIFIED BY EMERGENCY RESPONDERS.
 NUMBERS/LETTERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT
 WITH 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND.
  
 STRUCTURES WITH LIGHT FRAME ROOF TRUSS CONSTRUCTION
 SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO THE
 BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTER R.
  
 INDICATE THE LOCATION OF THE NEAREST FIRE HYDRANT(S).
  
 THE UNDERSIDE OF OF INTERIOR STAIRWAYS, IF OF
 COMBUSTIBLE CONSTRUCTION, SHALL BE PROTECTED TO PROVIDE
 NOT LESS THAN 1-HOUR FIRE RESISTANCE.
  
 THE EXIT STAIR ENCLOSURE IS NOT PERMITTED TO BE OPEN ON
 THE UPPER FLOOR.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 NO COOKING SHALL BE PERMITTED IN THE CONCESSION STAND
 UNLESS A TYPE I EXHAUST HOOD AND AUTOMATIC SUPPRESSION
 SYSTEM IS INSTALLED.
  