| Plan Review Notes For Permit 12110275 |
| Permit Number |
12110275 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-11-19 14:23:53 | 3401 PARKER AVENUE - PRESS BOX | | | PERMIT #12110275 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE A NAME, ADDRESS OR LETTER ON THE BUILDING SO | | | THE LOCATION CAN BE IDENTIFIED BY EMERGENCY RESPONDERS. | | | NUMBERS/LETTERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT | | | WITH 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND. | | | | | | STRUCTURES WITH LIGHT FRAME ROOF TRUSS CONSTRUCTION | | | SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO THE | | | BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS | | | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED | | | REFLECTIVE COLOR AND BEAR THE LETTER R. | | | | | | INDICATE THE LOCATION OF THE NEAREST FIRE HYDRANT(S). | | | | | | THE UNDERSIDE OF OF INTERIOR STAIRWAYS, IF OF | | | COMBUSTIBLE CONSTRUCTION, SHALL BE PROTECTED TO PROVIDE | | | NOT LESS THAN 1-HOUR FIRE RESISTANCE. | | | | | | THE EXIT STAIR ENCLOSURE IS NOT PERMITTED TO BE OPEN ON | | | THE UPPER FLOOR. | | | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | | EXIT SIGNS. | | | | | | NO COOKING SHALL BE PERMITTED IN THE CONCESSION STAND | | | UNLESS A TYPE I EXHAUST HOOD AND AUTOMATIC SUPPRESSION | | | SYSTEM IS INSTALLED. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|