| 2012-12-05 16:34:03 | BUILDING PLAN REVIEW |
| | PERMIT: 12110275 |
| | ADD: 3401 PARKER AVE |
| | CONT: HEDRICK BROTHERS |
| | CONTACT: DON JONES |
| | TEL: (561)689-8880 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW- PRESS BOX |
| | DEC. 5/ 2012 |
| | ACTION: DENIED |
| | |
| | 1) THE S-2 SHEET FOUNDATION NOTE # 4 INDICATES THERE TO |
| | BE A SOILS REPORT SUBMITTED. 2010 FBC-B 1803.1 GENERAL. |
| | GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED IN |
| | ACCORDANCE WITH SECTION 1803.2 AND REPORTED IN |
| | ACCORDANCE WITH SECTION 1803.6. WHERE REQUIRED BY THE |
| | BUILDING OFFICIAL OR WHERE GEOTECHNICAL INVESTIGATIONS |
| | INVOLVE IN-SITU TESTING, LABORATORY TESTING OR |
| | ENGINEERING CALCULATIONS, SUCH INVESTIGATIONS SHALL BE |
| | CONDUCTED BY A REGISTERED DESIGN PROFESSIONAL. |
| | |
| | 2) SHEET PBA-3 DETAIL # 1 AND SHEET PBS-3 DETAIL # 7 |
| | DEPICTS AN AREA OF CONCEALED HORIZONTAL TO VERTICAL |
| | SPACES REQUIRING FIRE BLOCKING PER 2010 FBC-B 717.2.3. |
| | |
| | 3) SHEET PBA-3 DETAIL # 1 WILL ALSO NEED FIRE BLOCKING |
| | AT THE TOP AND BOTTOM OF THE RUN. 2010 FBC-B 717.2.4 |
| | STAIRWAYS. FIREBLOCKING SHALL BE PROVIDED IN CONCEALED |
| | SPACES BETWEEN STAIR STRINGERS AT THE TOP AND BOTTOM OF |
| | THE RUN. ENCLOSED SPACES UNDER STAIRS SHALL ALSO COMPLY |
| | WITH SECTION 1009.6.3. |
| | |
| | 4) SHEET PBA-3 DETAIL # 1 THE PLUMBING CHASE VERSES THE |
| | STAIR STRINGERS, MISSING RATED CEILING. 2010 FBC-B |
| | 1009.6.3 ENCLOSURES UNDER STAIRWAYS. THE WALLS AND |
| | SOFFITS WITHIN ENCLOSED USABLE SPACES UNDER ENCLOSED |
| | AND UNENCLOSED STAIRWAYS SHALL BE PROTECTED BY 1-HOUR |
| | FIRE-RESISTANCE-RATED CONSTRUCTION OR THE |
| | FIRE-RESISTANCE RATING OF THE STAIRWAY ENCLOSURE, |
| | WHICHEVER IS GREATER. |
| | |
| | 5) SHEET PBA-3 DETAIL # 1 & 2 BOTH DEPICT AN ENLARGE |
| | DETAIL #2/ PBA 4 PLEASE PROVIDE CLARIFICATION BETWEEN |
| | THE WRITTEN STATEMENT AND DETAIL. IT APPEARS THE ROOF |
| | TILE WILL BE ATTACHED TO EITHER GYPSUM SHEATHING OR CDX |
| | PLYWOOD, IT APPEARS THAT THE INSULASION WILL BE |
| | SANDWICHED BETWEEN THE TWO LAYERS, PLEASE CLARIFY. THE |
| | CONCERNS ARE THAT THE FINISHED DECKING WILL MATCH WITH |
| | THE TYPE DECK FOUND IN THE ROOFING PRODUCT APPROVAL. |
| | THE SECOND ISSUE OR CONCERN IS THE 5 1/2 INCH THICK |
| | INSULATION APPEARS TO BE ON TOP OF THE TRUSSES, WHAT |
| | TYPE OF FASTENERS WILL BE HOLDING DOWN THE ROOF DECK? |
| | ADDITIONAL INFORMATION REQUIRED 107.1.2, |
| | |
| | 6) SHEET PBA-1 FIRST FLOOR PLAN, PLEASE PROVIDE |
| | MANUFACTURERS ADDITIONAL INFORMATION ON THE INCLINED |
| | STAIRWAY CHAIR LIFT. THE CHAIRLIFT WILL NEED TO COMPLY |
| | WITH : |
| | 2010 FBC-B 410.1 GENERAL. PLATFORM LIFTS SHALL COMPLY |
| | WITH ASME A18.1 (1999 EDITION OR 2003 EDITION) |
| | (INCORPORATED BY REFERENCE, SEE "REFERENCED STANDARDS" |
| | IN CHAPTER 1). PLATFORM LIFTS SHALL NOT BE |
| | ATTENDANT-OPERATED AND SHALL PROVIDE UNASSISTED ENTRY |
| | AND EXIT FROM THE LIFT. |
| | ADVISORY 410.1 GENERAL. |
| | INCLINED STAIRWAY CHAIRLIFTS AND INCLINED AND VERTICAL |
| | PLATFORM LIFTS ARE AVAILABLE FOR SHORT-DISTANCE |
| | VERTICAL TRANSPORTATION. BECAUSE AN ACCESSIBLE ROUTE |
| | REQUIRES AN 80 INCH (2030 MM) VERTICAL CLEARANCE, CARE |
| | SHOULD BE TAKEN IN SELECTING LIFTS AS THEY MAY NOT BE |
| | EQUALLY SUITABLE FOR USE BY PEOPLE USING WHEELCHAIRS |
| | AND PEOPLE STANDING. IF A LIFT DOES NOT PROVIDE 80 INCH |
| | (2030 MM) VERTICAL CLEARANCE, IT CANNOT BE CONSIDERED |
| | PART OF AN ACCESSIBLE ROUTE IN NEW CONSTRUCTION. |
| | THE ADA AND OTHER FEDERAL CIVIL RIGHTS LAWS REQUIRE |
| | THAT ACCESSIBLE FEATURES BE MAINTAINED IN WORKING ORDER |
| | SO THAT THEY ARE ACCESSIBLE TO AND USABLE BY THOSE |
| | PEOPLE THEY ARE INTENDED TO BENEFIT. BUILDING OWNERS |
| | ARE REMINDED THAT THE ASME A18 SAFETY STANDARD FOR |
| | PLATFORM LIFTS AND STAIRWAY CHAIRLIFTS REQUIRES ROUTINE |
| | MAINTENANCE AND INSPECTIONS. ISOLATED OR TEMPORARY |
| | INTERRUPTIONS IN SERVICE DUE TO MAINTENANCE OR REPAIRS |
| | MAY BE UNAVOIDABLE; HOWEVER, FAILURE TO TAKE PROMPT |
| | ACTION TO EFFECT REPAIRS COULD CONSTITUTE A VIOLATION |
| | OF FEDERAL LAWS AND THESE REQUIREMENTS. |
| | |
| | 7) SHEET PBA-1 THE ACCESSIBLE RESTROOM STALLS APPEAR TO |
| | HAVE A SIZE PROBLEM IN THE WIDTH THE PLANS TOTAL UP TO |
| | 7'-0" IN LENGTH. THE NEW 2010 FL ACCESSIBLITY CODE |
| | REQUIRES A 60 INCH CLEAR WIDTH FOR THE WATER CLOSET |
| | FROM THE WALL, THE LAVATORY CAN NOT PATRUDE INTO THIS |
| | SPACE (604.3.2). THE PLAN ALSO INDICATES THE LAV |
| | CENTERED 1'-7" FROM THE OTHER WALL. THAT ONLY ALLOWS |
| | FROM THE CENTER OF THE SINK TO THE 60 INCHES A |
| | MEASUREMENT OF 5 INCHES. THE MINIMUM ROOM SIZE THAT |
| | APPEARS TO WORK WOULD BE 7'-1" WITH THE SINK CENETERED |
| | AT 15 INCHES OFF THE WALL WITH A 19-20" LAV. FIGURE |
| | 604.8.1.6. |
| | |
| | 8) PBA-3 SCORERS TOWER IS INDICATED TO HAVE 439 SQ FT |
| | AND AN OPEN STAIRWELL, UNDER 2010 FBC-B 1022.1 |
| | EXCEPTION 1 AND OCCUPANT LOAD LESS THAN TEN AND 1.1 AND |
| | THE STAIRWAY IS OPEN TO NOT MORE THAN ONE STORY ABOVE |
| | ITS LEVEL OF EXIT DISCHARGE THIS IS ACCEPTABLE UNDER |
| | THE FBC. IF THE FIRE CODES ARE MORE STRINGENT THEN WE |
| | MUST GO WITH THE MOST STRINGENT OF THE TWO CODES. |
| | |
| | 9) PBA-3 SCORERS TOWER IF THE OPEN STAIRWELL IS TO STAY |
| | OPEN THEN THE STEM WALL WILL BECOME THE GAURD PLEASE |
| | PROVIDE A VERTICAL DIMENSION FOR THIS WALL PROVIDING |
| | CODE COMPLIANCE, 2010 FBC 1013.2 HEIGHTS 42 INCHES. |
| | |
| | 10) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 11) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING, FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | NOTE, THE PRESSURES FOR COMPONENTS & CLADDING ARE OK! |
| | IF THE CONTRACTOR ELECTS NOT SUBMIT PRODUCT APPROVALS |
| | BEFORE THE TIME OF PERMIT ISSUANCE THEN THEY WILL BE |
| | CONSIDERED REVISIONS AND ASSOCIATED REVIEWS AND FEES |
| | WILL OCCUR. A WRITTEN RESPONCE INDICATING PRODUCT |
| | APPROVALS WOULD BE SUBMITTED LATER WOULD PROVIDE AS |
| | WRITTEN NOTICE OF YOUR INTENT. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |