| 2013-02-11 15:26:05 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED: |
| | |
| | 1. NOT CLEAR WHICH PRODUCT IS PROPOSED. NOA 12-0209.06 |
| | SUBMITTED, INSTALLATION SCHEDULE REFERS TO NOA |
| | 12-0209.07. THE FOLLOWING REVIEW COMMENTS ARE BASED ON |
| | THE NOA SUBMITTED, 12-0209.06. |
| | |
| | 2. SEE COLUMN: SHUTTER MOUNTING CONNECTION TYPE PER |
| | PRODUCT APPROVAL. THIS SHOULD CORRELATE WITH THE ANCHOR |
| | DETAILS ON SHEET 12 (FOR WOOD STRUCTURES). |
| | |
| | 4TH REVIEW, STATES LAG SCREWS. THIS IS THE FASTENER. |
| | PROVIDE CONNECTION TYPE PROPOSED; ALTERNATIVE 1 THROUGH |
| | ALTERNATIVE 8. PLEASE NOTE THAT 6" FASTENING APPEARS TO |
| | COMPLY FOR ALL CONNECTION TYPES BUT LAG SCREWS NOT THE |
| | CORRECT FASTENER FOR ALL CONNECTION TYPES. |
| | |
| | 3. OK. |
| | |
| | 4. IF NOA 12-0209.07 IS PROPOSED, PLEASE PROVIDE TWO |
| | SETS OF PRODUCT APPROVALS. IF NOA 12-0209.07 IS |
| | PROPOSED, REVISE INSTALLATION SCHEDULE AND RESUBMIT. |
| | |
| | NOT ADDRESSED. PLEASE CLARIFY WHICH PRODUCT IS TO BE |
| | INSTALLED. NOA #12-0209.06 SUBMITTED, BUT INSTALLATION |
| | SCHEDULE PROPOSES 12-0209.07. |
| | |
| | NEW COMMENT: |
| | |
| | PREVIOUS INSTALLATION SCHEDULES HAD FOUR OPENINGS, THIS |
| | ONE HAS TWO. PLEASE INCLUDE ALL OPENINGS OR OTHERWISE |
| | PROVIDE IMPACT PROTECTION FOR OPENINGS 1 AND 4 WHICH |
| | WERE NOT INCLUDED ON THE LATEST INSTALLATION SCHEDULE. |
| | |