| Plan Review Notes For Permit 12110270 |
| Permit Number |
12110270 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-12-20 11:28:39 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. FOR THE SHUTTERS, COMPLETE THE SAMPLE INSTALLATION | | | SCHEDULE (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITY | | | OFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PD | | | F) OR PROVIDE ALL INFORMATION IN AN ALTERNATE FORMAT. | | | | | | 2ND REVIEW, THE FOLLOWING INFORMATION IS REQUIRED: | | | | | | SHUTTER MOUNTING CONNECTION TYPE | | | SHUTTER GLASS SEPARATION | | | SHUTTER SPAN | | | SHUTTER INSTALLED VERT/HORIZONTAL | | | EDGE DISTANCE | | | SUBSTRATE | | | | | | THIS CANNOT BE REDLINED FOR YOU AS JOB CONDITIONS WILL | | | DETERMINE SHUTTER CONNECTION MOUNTING TYPE (THIS SHOULD | | | CORRELATE WITH ANCHOR SCHEDULES, FOR EXAMPLE 1 TOP, | | | THROUGH 11 BOTTOM, AND EITHER CONNECTION CAN BE USED ON | | | HORIZONTAL APPLICATIONS). | | | |
|