| Plan Review Notes For Permit 12110167 |
| Permit Number |
12110167 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-11-13 14:57:25 | 2010 FBC | | | | | | REVISION IS DENIED BY BUILDING | | | | | | 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED NOA NO. | | | 08-0221.04 HAS BEEN SUPERSEDED BY NOA NO.08-0922.04. | | | PLEASE SUBMIT THE CURRENT PRODUCT APPROVAL. DCA RULE | | | 9N-3 | | | | | | 2) THE ENGINEERING SPECIFIES AN ALLOWABLE UPLIFT | | | PRESSURE OF -457.5 PSF FOR THE APPROVED ASSEMBLY THAT | | | WILL BE INSTALLED. THE ASSEMBLY WITH THIS MAXIMUM | | | DESIGN PRESSURE IS FOR NON-INSULATED CONCRETE DECKS. | | | HOWEVER, THE APPROVED ASSEMBLY THAT WAS SUBMITTED (PAGE | | | 8 OF 27) IS FOR AND INSULATED CONCRETE DECK WITH A | | | MAXIMUM DESIGN PRESSURE OF -140 PSF. PLEASE CORRECT. | | | CITY AMENDMENTS 107.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|