| Plan Review Notes For Permit 12110149 |
| Permit Number |
12110149 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-11-26 14:31:22 | 12110149 | | | 515 PALM STREET | | | CHANGE OF USE | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENT. | | | | | | PROVIDE AN ELECTRICAL PLAN SHOWING LOCATION OF ALL | | | LIGHTING, RECEPTACLES AND THE PANELBOARD. INDICATE THE | | | WIRING METHOD USED (IE. ARMORED CABLE, METAL CLAD | | | CABLE, OR CONDUIT). NEC 215.5 | | | ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINK MUST | | | BE GFCI PROTECTED. NEC 210.8 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|