1 |
|
| Notes |
| Date |
Text |
| 2012-11-06 13:30:57 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. FOR THE SHUTTERS, COMPLETE THE SAMPLE INSTALLATION | | | SCHEDULE OR PROVIDE ALL INFORMATION TO SHOW CODE | | | COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC R301, | | | FBC1609. TWO SETS REQUIRED. THIS FORM IS AVAILABLE IN | | | THE LOBBY OR ON THE INTERNET AT | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ | | | INSTALLATION.PDF | | | | | | 2. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL | | | BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE | | | INSTALLATION SCHEDULE, ITEM 2 ABOVE. FBC R301, FBC1609, | | | FBC*106. | | | | | | 3. FOR THE WINDOWS, PROVIDE A FLOOR PLAN SHOWING: | | | WINDOW LOCATIONS, SIZES, WINDOW TYPE, ROOM | | | DESIGNATIONS. NOTE EXISTING CONDITIONS (TYPE OF WINDOW) | | | AND OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1. | | | THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%. | | | | | | 4. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4. | | | | | | |
|