| Plan Review Notes For Permit 12100955 |
| Permit Number |
12100955 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-11-01 17:36:25 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. ENHANCED FASTENING TO BE CALCULATED BY AN ARCHITECT, | | | ENGINEER, OR REGISTERED ROOF CONSULTANT, SEE LAST PAGE | | | OF NOA, GENERAL LIMITATION #7, FBC RESIDENTIAL 301. | | | | | | 2. DOUBLE UNDERLAYMENT REQUIRED FOR SHINGLE ROOFS WHEN | | | SLOPE IS LESS THAN 4/12, FBC 1507.2.8. | | | | | | 3. CONTRACTOR IS REQUIRED TO SIGN THE PERMIT | | | APPLICATION, FS 553. | | | | | | | | | |
|