| Notes |
| Date |
Text |
| 2012-11-15 09:48:48 | | | | 12100920 | | | 901 45TH STREET | | | GENERATOR INSTALLATION | | | | | | PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW | | | COMMENTS. | | | | | | VERIFY THE REQUIRED SAFETY CLEARANCES ARE BEING | | | OBSERVED WITHIN THE GENERATOR ENCLOSURE TO ALL | | | ELECTRICAL EQUIPMENT. NEC 110.26 | | | | | | INDICATE THE FEEDER CONDUCTOR SIZE PROPOSED FROM THE | | | NEW GENERATOR TO THE SWITCHBOARD. | | | NEC 445.13 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|