Plan Review Notes
Plan Review Notes For Permit 12100900
Permit Number 12100900
Review Stop M
Sequence Number 2
Notes
Date Text
2013-03-13 09:02:12PLANS DENIED
 1) REFER TO SECTION 503.2.1 CALCULATION FOR HEATING &
 COOLING LOADS.
 2010 FLORIDA ENERGY CODE
 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS.
 FOR FRESH AIR
 2010 FLORIDA ENERGY CODE.
 3) COMPLETE THE EQUIPMENT SCHEDULE ON THE PLANS PER
 SECTION 107
 PLANS SHOW THREE A/C SYSTEMS SCHEDULE SHOWS TWO A/C
 SYSTEMS.
 2010 FBC.
 4) SHOW FRESH AIR DUCT ON THE MECHANICAL PLANS PER
 SECTION 107
 2010 FBC.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]