| Permit Number |
12100900 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-03-13 09:02:12 | PLANS DENIED | | | 1) REFER TO SECTION 503.2.1 CALCULATION FOR HEATING & | | | COOLING LOADS. | | | 2010 FLORIDA ENERGY CODE | | | 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS. | | | FOR FRESH AIR | | | 2010 FLORIDA ENERGY CODE. | | | 3) COMPLETE THE EQUIPMENT SCHEDULE ON THE PLANS PER | | | SECTION 107 | | | PLANS SHOW THREE A/C SYSTEMS SCHEDULE SHOWS TWO A/C | | | SYSTEMS. | | | 2010 FBC. | | | 4) SHOW FRESH AIR DUCT ON THE MECHANICAL PLANS PER | | | SECTION 107 | | | 2010 FBC. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|