Date Text
2012-11-19 16:19:3412100900
 4200 BROADWAY
 COMMERCIAL RENOVATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE A RISER PLAN SHOWING THE EXISTING ELECTRIC
 SERVICE COMPONENTS WITH METERS, MAIN DISCONNECTS AND
 PANEL BOARDS. NEC 110.26, 215.5, 240.24
 VERIFY THE REQUIRED WORKING CLEARANCES AND DEDICATED
 WORKING SPACE HAS BEEN PROVIDED AT THE ELECTRICAL
 SERVICE. NEC 110.26, 240.24
 VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING
 ARE SIX OR LESS AND GROUPED IN ONE LOCATION. NEC 230.2,
 230.71, 230.72
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  