| Plan Review Notes For Permit 12100900 |
| Permit Number |
12100900 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-11-19 16:19:34 | 12100900 | | | 4200 BROADWAY | | | COMMERCIAL RENOVATION | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | PROVIDE A RISER PLAN SHOWING THE EXISTING ELECTRIC | | | SERVICE COMPONENTS WITH METERS, MAIN DISCONNECTS AND | | | PANEL BOARDS. NEC 110.26, 215.5, 240.24 | | | VERIFY THE REQUIRED WORKING CLEARANCES AND DEDICATED | | | WORKING SPACE HAS BEEN PROVIDED AT THE ELECTRICAL | | | SERVICE. NEC 110.26, 240.24 | | | VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING | | | ARE SIX OR LESS AND GROUPED IN ONE LOCATION. NEC 230.2, | | | 230.71, 230.72 | | | PROVIDE A LIGHTING DENSITY CALCULATION SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | | REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|