2012-11-09 15:42:132010 FBC
  
 1) THE WALL SECTION ON SHEET 1 SPECIFIES R-19 ATTIC
 INSULATION AND THE ENERGY CALCULATION FORM LISTS R-30
 INSULATION. PLEASE CORRECT. FBC ENERGY CONSERVATION
 405.4.2
  
 2) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED
 BY THE OWNER/AGENT. FBC ENERGY CONSERVATION 405.4.2
  
 3) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 OVERHEAD GARAGE DOORS AND THE ASPHALT ROOF SHINGLES AS
 REQUIRED BY DCA RULE 9N-3.
  
 4) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. CITY AMENDMENTS 107.3.4.1
  