| Plan Review Notes For Permit 12100772 |
| Permit Number |
12100772 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-12-03 16:16:11 | *** MECHANICAL CORRETCIONS TO BE MADE. | | | | | | 1) MECHANICAL PLAN SUBMITTED WITH COOLING LOAD CAL'S. | | | SHOWS NO INFORMATION REGARDING DUCT DESIGN EQUIPMENT | | | INFO. ETC. PLEASE SUBMIT MECHANICAL PLANS, PER 2010 | | | CITY OF WPB AMEND. 107.3.5.3 (10). | | | | | | 2) DUCT SYSTEM SUMMARY SUBMITTED OFFERS LITTLE, TOO NO | | | INFORMATION REGARDING THE CALCULATIONS. PLEASE SUBMIT | | | MANUAL D CAL'S. OR EQUIVALENT, PER 2010 FBC/R M1601.1. | | | | | | 3) PLEASE HAVE ENERGY CAL'S. SIGNED AND DATED BY THE | | | OWNER/AGENT, PER 2010 FBC ENERGY 103.2.3.2. | | | | | | *** MACHANICAL PLAN REVIEW BY TOM GORDON (HY-BYRD INC.) | | | *** FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710 |
|