| Plan Review Notes For Permit 12100750 |
| Permit Number |
12100750 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-11-02 10:51:54 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. THE PRODUCT APPROVAL SUBMITTED, JOHNS MANVILLE | | | MODIFIED FOR WOOD DECK, IS EXPIRED. PLEASE PROVIDE TWO | | | SETS OF THE CURRENT PRODUCT APPROVAL FOR THIS PROJECT | | | (POSSIBLY NOA 12-0203.03). | | | | | | 2. PLEASE PROVIDE THE FOLLOWING INFORMATION: MEAN ROOF | | | HEIGHT, PARAPET INFORMATION (IN ORDER TO DETERMINE | | | REQUIRED DESIGN PRESSURES) FBC RESIDENTIAL 301. | | | | | | 3. SEE GENERAL LIMITATION #7 ON THE PRODUCT APPROVAL. | | | ENHANCED FASTENING IN ACCORDANCE WITH RAS 117 IS | | | REQUIRED TO BE CALCULATED BY AN ARCHITECT, ENGINEER, OR | | | REGISTERED ROOF CONSULTANT. PLEASE PROVIDE. | | | | | | 4. ON THE PRODUCT APPROVAL, INDICATE WHICH APPROVED | | | ASSEMBLY WAS INSTALLED, FBC 106, FBC RESIDENTIAL 301. | | | | | | |
|