2012-11-02 10:51:54****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. THE PRODUCT APPROVAL SUBMITTED, JOHNS MANVILLE
 MODIFIED FOR WOOD DECK, IS EXPIRED. PLEASE PROVIDE TWO
 SETS OF THE CURRENT PRODUCT APPROVAL FOR THIS PROJECT
 (POSSIBLY NOA 12-0203.03).
  
 2. PLEASE PROVIDE THE FOLLOWING INFORMATION: MEAN ROOF
 HEIGHT, PARAPET INFORMATION (IN ORDER TO DETERMINE
 REQUIRED DESIGN PRESSURES) FBC RESIDENTIAL 301.
  
 3. SEE GENERAL LIMITATION #7 ON THE PRODUCT APPROVAL.
 ENHANCED FASTENING IN ACCORDANCE WITH RAS 117 IS
 REQUIRED TO BE CALCULATED BY AN ARCHITECT, ENGINEER, OR
 REGISTERED ROOF CONSULTANT. PLEASE PROVIDE.
  
 4. ON THE PRODUCT APPROVAL, INDICATE WHICH APPROVED
 ASSEMBLY WAS INSTALLED, FBC 106, FBC RESIDENTIAL 301.
  
  