2012-11-07 16:46:142010 FBC
  
 DENIED BY BUILDING
  
 1) THE PLANS THAT WERE SUBMITTED ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT SPECIFIED IN THE
 TITLE BLOCK PER FS 481.
  
 2) THE PLANS HAVE BEEN REDUCED IN SIZE FROM THE
 ORIGINAL 1/4" SCALE AND ARE TOO SMALL. CITY AMENDMENT
 107.2.1.4 REQUIRES PLANS TO BE A MINIMUM SCALE OF 1/8"
 SCALE. PLEASE CORRECT.
  
 3) THERE ARE NO DIMENSIONS ON THE PLANS. PROVIDE
 DIMENSIONED FLOOR PLANS. CITY AMENDMENT 107.2.1
  
 4) ON SHEET SP-1 THE WRONG CODE EDITION AND DESIGN
 CRITERIA IS SPECIFIED FOR THE PROJECT INFORMATION. THE
 WINDOW AND DOOR PRESSURES LISTED ARE TOO LOW FOR
 EXPOSURE C WITH A 25' MRH. THE PRESSURES FOR A 10 SQFT
 OPENING IN WALL ZONE 5 WOULD BE +42.3, -56.6 PSF PER
 FBCR 301.2.1.
  
 5) TWO PRODUCT APPROVALS WERE SUBMITTED FOR TRACO
 SINGLE HUNG WINDOWS. THERE IS NO MENTION OF WINDOW
 REPLACEMENT ON THE APPLICATION OR IN THE SCOPE OF WORK
 ON THE PLANS. PLEASE CLARIFY. NOTE: THESE PRODUCT
 APPROVALS EXPIRED IN 2007.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]