| 2012-10-29 09:47:52 | 12050341 | | | 1711 LONGWOOD ROAD | | | NEW ELECTRIC SYSTEM | | | | | | FEEDERS TO PANEL BOARD ?PM2? MAY NOT BE DIVIDED BETWEEN | | | TWO CONDUITS. ALL CONDUCTORS OF THE SAME CIRCUIT SHALL | | | BE CONTAINED WITHIN THE SAME RACEWAY. NEC 300.3 (B) | | | | | | PROVIDE A COMMON GROUNDING ELECTRODE CONDUCTOR FOR THE | | | MULTIPLE SEPARATELY DERIVED SYSTEMS WHICH TIES BACK TO | | | THE SERVICE. NEC 250.30 (4), 250.52. | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | | | | |
|