FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2013-01-04 10:42:56 | 801 VILLAGE BOULEVARD - SUITE #303-304 | | | PERMIT #12100670 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | REPEAT COMMENT: NO ADDRESS PROVIDED IN THE PLAN | | | TITLEBLOCK INFORMATION. | | | | | | REPEAT COMMENT: ENGINEERED FIRE SPRINKLER CONSTRUCTION | | | DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT. | | | AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE | | | SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS | | | (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) | | | FOR A SUB-PERMIT. | | | | | | REPEAT COMMENT: PER FLORIDA ADMINISTRATIVE CODE SECTION | | | 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS | | | SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER | | | SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE | | | TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR | | | EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN | | | DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT | | | FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION | | | SUCH AS PRE-ENGINEERED SYSTEMS. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|