Plan Review Notes
Plan Review Notes For Permit 12100670
Permit Number 12100670
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2012-12-17 09:19:42801 VILLAGE BOULEVARD - SUITE #303-304
 PERMIT #12100670
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: NO ADDRESS PROVIDED IN THE PLAN
 TITLEBLOCK INFORMATION.
  
 NEW COMMENT: REVISE THE OCCUPANT LOAD CHART TO MATCH
 THE OCCUPANT LOADS SHOWN ON THE FLOOR PLAN.
 ORIGINAL COMMENT: PER TABLE 7.3.1.2 (NFPA 101 -
 FLORIDA) THE DAY-CARE OCCUPANT LOAD FACTOR SHALL BE 20
 SQ.FT. PER PERSON NOT 35 SQ.FT. PER PERSON.
  
 REPEAT COMMENT: ELECTRICAL - NO MANUAL FIRE ALARM
 SYSTEM OR SMOKE DETECTION PROVIDED PER SECTION 16.3.4
 (NFPA 101 - FLORIDA).
  
 REPEAT COMMENT: ENGINEERED FIRE ALARM AND FIRE
 SPRINKLER CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A
 GENERAL BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS
 BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT.
  
 REPEAT COMMENT: PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730