| 2012-12-17 09:19:42 | 801 VILLAGE BOULEVARD - SUITE #303-304 |
| | PERMIT #12100670 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | REPEAT COMMENT: NO ADDRESS PROVIDED IN THE PLAN |
| | TITLEBLOCK INFORMATION. |
| | |
| | NEW COMMENT: REVISE THE OCCUPANT LOAD CHART TO MATCH |
| | THE OCCUPANT LOADS SHOWN ON THE FLOOR PLAN. |
| | ORIGINAL COMMENT: PER TABLE 7.3.1.2 (NFPA 101 - |
| | FLORIDA) THE DAY-CARE OCCUPANT LOAD FACTOR SHALL BE 20 |
| | SQ.FT. PER PERSON NOT 35 SQ.FT. PER PERSON. |
| | |
| | REPEAT COMMENT: ELECTRICAL - NO MANUAL FIRE ALARM |
| | SYSTEM OR SMOKE DETECTION PROVIDED PER SECTION 16.3.4 |
| | (NFPA 101 - FLORIDA). |
| | |
| | REPEAT COMMENT: ENGINEERED FIRE ALARM AND FIRE |
| | SPRINKLER CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A |
| | GENERAL BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS |
| | BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP |
| | DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION |
| | DOCUMENTS) FOR A SUB-PERMIT. |
| | |
| | REPEAT COMMENT: PER FLORIDA ADMINISTRATIVE CODE SECTION |
| | 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS |
| | SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER |
| | SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE |
| | TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR |
| | EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN |
| | DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT |
| | FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION |
| | SUCH AS PRE-ENGINEERED SYSTEMS. |
| | |