Plan Review Notes
Plan Review Notes For Permit 12100670
Permit Number 12100670
Review Stop B
Sequence Number 2
Notes
Date Text
2012-12-12 16:25:22BUILDING PLAN REVIEW
 PERMIT: 12100670
 ADD: 801 VILLAGE BLVD # 303-304
 CONT: PAGE CONTRACING
 TEL: (954)868-4561
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DEC. 12/ 2012
 ACTION:DENIED
  
 1) SHEET A-2.01:
  
 1A) COMPLIED.
  
 1B) 2ND REQUEST PLEASE REVIEW OCCUPANT LOAD CHART AND
 TOTAL OCCUPANCY LOAD. 2010 FBC-B TABLE 1004.1.1 FOR
 DAYCARE THE OCCUPANT LOAD IS FIGURED AT 20 NET NOT THE
 35 SQ FT AS INDICATED, THE OFFICE, LOBBY AND KITCHEN DO
 NOT INDICATE ANY OCCUPANT LOADS WITHIN THE CHART BUT
 THE FLOOR PLAN DOES, PLEASE CORRECT THE OCCUPANT LOAD
 FOR EACH ROOM WITHIN THE CHART, CORRECT THE SQ FT
 REQUIRED FOR EACH OCCUPANT PER TABLE 1004.1. AAND
 PROVIDE THE TOTAL OCCUPANT LOAD FOR THE DAYCARE
 OCCUPANCY.
 2) SHEET A2.01:
  
 2A) COMPLIED.
  
 2B) COMPLIED.
  
 3) COMPLIED.
  
 4) 2ND REQUEST, SHEET E1 NOR THE LIFE SAFETY SHEEET
 INDICATE COMPLIANCE WITH2010 EXISTING BLDG CODE 912.2.2
 FIRE ALAARM AND DETECTION SYSTEMS AND 2010 FBC-B 436.7
 DETECTION AND ALARM SYSTEMS . THE RESPONSE INDICATES
 THAT FIRE ALARM AND FIRE SPRINKLER DRAWINGS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT BUT NONE HAVE
 BEEN PROVIDED.
 2010 WPB ADMINISTRATIVE CODE. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFICAND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART...
  
 5) COMPLIED..
  
 6) 2ND REQUEST. PLANSDO NOT INDICATE WALL FINISHES FOR
 SPRINKLERED BUILDING PROVIDE COMPLIANCE WITH TABLE
 803.9 AND 806.1.2 COMBUSTIBLE DECORATIVE MATERIALS.
  
 7) 2ND REQUEST. SHEET A2.02 THE NEW SIDEWALKS ON THE
 BUILDING ARE 5'-0" WIDE CODE COMPLIANT FOR AN
 ACCESSIBLE ENTRANCE AS DEPICTED IN FIGURE 404.2.4.1 (D)
 REQUIRING 60" BUT THE NEW SIDEWALK ON THE SIDE OF THE
 BUILDING IS ONLY 4'-0" WIDE A NEW NON-CODE COMPLIANT
 ELEMENT, THE PORTION THAT IS DIRECTLY AGAINST THE
 BUILDING.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  