| Plan Review Notes For Permit 12100670 |
| Permit Number |
12100670 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-12-05 09:59:21 | *** CORRECTIONS NEED TO MECHANICAL PLANS*** | | | | | | 1) MECHANICAL PLAN M1, ROOM #112 HAS EF-1 EXHAUSTION 80 | | | CFM'S FROM THE ROOM, THE A/C DUCT IS ONLY SUPPLYING 75 | | | CFM'S OF AIR TO THE ROOM, THIS WOULD PUT THE ROOM AT A | | | NEGATIVE PRESSURE. THE CLOTHES DRYER MAY NOT BE ABLE TO | | | DISCHARGE TO THE ROOF WHEN THE ROOM IS AT A NEGATIVE | | | PRESSURE. PLEASE PROVIDE DOCUMENTATION FROM THE | | | MANUFACTURE OF THE DRYER SHOWING THE EQUIPMENT CAN | | | OPERATE CORRECTLY UNDER THIS ENVIRONMENT, OR PLEASE | | | CORRECT. SEE 2010 FBC/M 304.1. | | | | | | 2) AHU'S 1, 2, 5, & 7 NEED TO SHOW THE OUTDOOR AIR (FA) | | | IS BEING DUCTED TO THE ROOF, PLEASE CORRECT. SEE 2010 | | | FBC/M 401.4. | | | | | | 3) PLAN M-1 SHOWS A RETURN AIR GRILL IN THE KITCHEN | | | (ROOM 111). PER 2010 FBC/M 407.1 RETURN AIR MAY NOT BE | | | TAKEN FROM A KITCHEN, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY TOM GORDON (HY-BYRD INC.) | | | FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710 |
|