2012-12-05 09:59:21*** CORRECTIONS NEED TO MECHANICAL PLANS***
  
 1) MECHANICAL PLAN M1, ROOM #112 HAS EF-1 EXHAUSTION 80
 CFM'S FROM THE ROOM, THE A/C DUCT IS ONLY SUPPLYING 75
 CFM'S OF AIR TO THE ROOM, THIS WOULD PUT THE ROOM AT A
 NEGATIVE PRESSURE. THE CLOTHES DRYER MAY NOT BE ABLE TO
 DISCHARGE TO THE ROOF WHEN THE ROOM IS AT A NEGATIVE
 PRESSURE. PLEASE PROVIDE DOCUMENTATION FROM THE
 MANUFACTURE OF THE DRYER SHOWING THE EQUIPMENT CAN
 OPERATE CORRECTLY UNDER THIS ENVIRONMENT, OR PLEASE
 CORRECT. SEE 2010 FBC/M 304.1.
  
 2) AHU'S 1, 2, 5, & 7 NEED TO SHOW THE OUTDOOR AIR (FA)
 IS BEING DUCTED TO THE ROOF, PLEASE CORRECT. SEE 2010
 FBC/M 401.4.
  
 3) PLAN M-1 SHOWS A RETURN AIR GRILL IN THE KITCHEN
 (ROOM 111). PER 2010 FBC/M 407.1 RETURN AIR MAY NOT BE
 TAKEN FROM A KITCHEN, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY TOM GORDON (HY-BYRD INC.)
 FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710