2012-10-29 13:18:26801 VILLAGE BOULEVARD - SUITE #303-304
 PERMIT #12100670
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION.
  
 PLEASE PROVIDE A NOTE ON THE LIFE SAFETY PLAN
 INDICATING THE FOLLOWING INFORMATION:
  
 1) ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 SHALL NOT EXCEED 50 PERCENT OF THE INDIVIDUAL WALL
 AREA.
  
 2) AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN
 BUILDING PRIOR TO OCCUPANCY.
  
 3) EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY.
 ALL DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM.
  
 4) FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED
 MONTHLY BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER
 WHICH A COPY OF THE LATEST INSPECTION REPORT SHALL BE
 POSTED IN A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY.
 IT SHALL BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS
 DAILY TO ENSURE THAT ALL DOORS AND EXIT PATHS ARE
 MAINTAINED CLEAR OF OBSTRUCTIONS.
  
 TRASH AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN
 DESIGNATED EXTERIOR AREAS. ALL OTHER DEMOLITION OR
 CONSTRUCTION AREAS SHALL HAVE "NO SMOKING" SIGNS
 POSTED. WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES
 FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 PER TABLE 7.3.1.2 (NFPA 101 - FLORIDA) THE DAY-CARE
 OCCUPANT LOAD FACTOR SHALL BE 20 SQ.FT. PER PERSON NOT
 35 SQ.FT. PER PERSON.
  
 CONFIRM EXISTING DOORS IN LOBBY #101 ARE EQUIPPED WITH
 PANIC HARDWARE.
  
 EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO ALLOW
 OPENING OF THE LOCKED DOOR FROM THE OUTSIDE BY AN
 OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE TO THE
 STAFF.
  
 EACH SMOKE OR FIRE-RATED BARRIER SHALL BE PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM, CORRIDOR WALLS
 SHALL NOT BE REQUIRED TO BE FIRE RATED PROVIDED THAT
 SUCH WALLS FORM SMOKE PARTITIONS.
  
 SHEET E-2: NO EXIT SIGN AND EMERGENCY LIGHT HAS BEEN
 PROVIDED FOR THE SECONDARY EXIT DOOR.
  
 ELECTRICAL: NO MANUAL FIRE ALARM SYSTEM OR SMOKE
 DETECTION PROVIDED PER SECTION 16.3.4 (NFPA 101 -
 FLORIDA).
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  