 COMMERCIAL REMODEL ? DAYCARE
  
 PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW
 COMMENTS.
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
 ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GFCI PROTECTION. NEC 422.52
 ALL RECEPTACLES LOCATED WITH IN SIX FEET OF A SINK MUST
 BE GFCI PROTECTED. NEC 210.8
 A FIRE ALARM SYSTEM IS REQUIRED. FBC 436.7
 A SMOKE DETECTION SYSTEM IS REQUIRED. FBC 436.7.2
  
 NOTE:
 SEPARATE PERMITS ARE REQUIRED FOR VOICE AND DATA AND
 ALARM SYSTEMS.
  
  