| 2012-11-14 09:41:15 | BUILDING PLAN REVIEW |
| | PERMIT: 12100670 |
| | ADD: 801 VILLAGE BLVD # 303-304 |
| | CONT: PAGE CONTRACING |
| | TEL: (954)868-4561 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | NOV. 14/ 2012 |
| | ACTION:DENIED |
| | |
| | 1) SHEET A-2.01: |
| | |
| | 1A) BUILDING DATA CHART INDICATES THIS IS A LEVEL II |
| | ALTERATION. 2010 EXISTING BUILDING CODE PLEASE REVIEW |
| | 901.3.1 PARTIAL CHANGE OF OCCUPANCY AND 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | THIS IS A CHANGE IN OCCUPANCY GOING FROM BUSINESS TO |
| | DAYCARE. |
| | |
| | 1B) PLEASE REVIEW OCCUPANT LOAD CHART AND TOTAL |
| | OCCUPANCY LOAD. 2010 FBC-B TABLE 1004.1.1 FOR DAYCARE |
| | THE OCCUPANT LOAD IS FIGURED AT 20 NET NOT THE |
| | 35 SQ FT AS INDICATED, THE TOTAL OCCUPANT LOAD IS |
| | APPROXIMATELY 214 WITH THE SQ FT INCLUDED FOR OFFICE |
| | STAFF. |
| | |
| | 2) SHEET A2.01: |
| | |
| | 2A) THE HARDWARE SCHEDULE DOESN'T INDICATE COMPLIANCE |
| | WITH 436.3 BATHROOM DOORS. |
| | |
| | 2B) PLEASE REVIEW REQUIREMENTS FOR THE MAINTENACE ROOM/ |
| | LAUNDRY UNDER 2010 FBC-B 436.6.2 FOR THE REQUIREMENT OF |
| | A 1 HOUR FIRE RATING OF WALLS AND OPENING PROTECTION IN |
| | ACCORDANCE WITH TABLE 715.4. |
| | |
| | 3) THE E1 SHEET INDICATES THE USE OF EXIT LIGHTS AND |
| | BATTERY BACK UP ILLUMINATION UNITS WITH THE CORRIDOR |
| | 103. 2010 FBC-B TABLE 1006. |
| | |
| | 4) SHEET E1 NOR THE LIFE SAFETY SHEEET INDICATE |
| | COMPLIANCE WITH2010 EXISTING BLDG CODE 912.2.2 FIRE |
| | ALAARM AND DETECTION SYSTEMS AND 2010 FBC-B 436.7 |
| | DETECTION AND ALARM SYSTEMS . |
| | |
| | 5) SHEET A-2.1 INDICATES THE EXIT CORRIDOR WALLS TO BE |
| | A WALL TAG TYPE D, AND NO INFORMATION ON THE CORRIDOR |
| | CEILING TYPE, PLEASE PROVIDE COMPLIANCE WITH |
| | 2010 FBC-B 436.8 CORRIDORS EXCEPTION # 1 CORRIDOR WALLS |
| | FORMING SMOKE PARTITIONS IN ACCORDANCE WWITH 710. |
| | |
| | 6) PLANSDO NOT INDICATE WALL FINISHES FOR SPRINKLERED |
| | BUILDING PROVIDE COMPLIANCE WITH TABLE 803.9 AND |
| | 806.1.2 COMBUSTIBLE DECORATIVE MATERIALS. |
| | |
| | 7) SHEET A2.02 THE NEW SIDEWALKS ON THE BUILDING ARE |
| | 5'-0" WIDE CODE COMPLIANT FOR AN ACCESSIBLE ENTRANCE AS |
| | DEPICTED IN FIGURE 404.2.4.1 (D) REQUIRING 60" BUT THE |
| | NEW SIDEWALK ON THE SIDE OF THE BUILDING IS ONLY 4'-0" |
| | WIDE A NEW NON-CODE COMPLIANT ELEMENT. |
| | |
| | 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |