Plan Review Notes
Plan Review Notes For Permit 12100670
Permit Number 12100670
Review Stop B
Sequence Number 1
Notes
Date Text
2012-11-14 09:41:15BUILDING PLAN REVIEW
 PERMIT: 12100670
 ADD: 801 VILLAGE BLVD # 303-304
 CONT: PAGE CONTRACING
 TEL: (954)868-4561
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 NOV. 14/ 2012
 ACTION:DENIED
  
 1) SHEET A-2.01:
  
 1A) BUILDING DATA CHART INDICATES THIS IS A LEVEL II
 ALTERATION. 2010 EXISTING BUILDING CODE PLEASE REVIEW
 901.3.1 PARTIAL CHANGE OF OCCUPANCY AND 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 THIS IS A CHANGE IN OCCUPANCY GOING FROM BUSINESS TO
 DAYCARE.
  
 1B) PLEASE REVIEW OCCUPANT LOAD CHART AND TOTAL
 OCCUPANCY LOAD. 2010 FBC-B TABLE 1004.1.1 FOR DAYCARE
 THE OCCUPANT LOAD IS FIGURED AT 20 NET NOT THE
 35 SQ FT AS INDICATED, THE TOTAL OCCUPANT LOAD IS
 APPROXIMATELY 214 WITH THE SQ FT INCLUDED FOR OFFICE
 STAFF.
  
 2) SHEET A2.01:
  
 2A) THE HARDWARE SCHEDULE DOESN'T INDICATE COMPLIANCE
 WITH 436.3 BATHROOM DOORS.
  
 2B) PLEASE REVIEW REQUIREMENTS FOR THE MAINTENACE ROOM/
 LAUNDRY UNDER 2010 FBC-B 436.6.2 FOR THE REQUIREMENT OF
 A 1 HOUR FIRE RATING OF WALLS AND OPENING PROTECTION IN
 ACCORDANCE WITH TABLE 715.4.
  
 3) THE E1 SHEET INDICATES THE USE OF EXIT LIGHTS AND
 BATTERY BACK UP ILLUMINATION UNITS WITH THE CORRIDOR
 103. 2010 FBC-B TABLE 1006.
  
 4) SHEET E1 NOR THE LIFE SAFETY SHEEET INDICATE
 COMPLIANCE WITH2010 EXISTING BLDG CODE 912.2.2 FIRE
 ALAARM AND DETECTION SYSTEMS AND 2010 FBC-B 436.7
 DETECTION AND ALARM SYSTEMS .
  
 5) SHEET A-2.1 INDICATES THE EXIT CORRIDOR WALLS TO BE
 A WALL TAG TYPE D, AND NO INFORMATION ON THE CORRIDOR
 CEILING TYPE, PLEASE PROVIDE COMPLIANCE WITH
 2010 FBC-B 436.8 CORRIDORS EXCEPTION # 1 CORRIDOR WALLS
 FORMING SMOKE PARTITIONS IN ACCORDANCE WWITH 710.
  
 6) PLANSDO NOT INDICATE WALL FINISHES FOR SPRINKLERED
 BUILDING PROVIDE COMPLIANCE WITH TABLE 803.9 AND
 806.1.2 COMBUSTIBLE DECORATIVE MATERIALS.
  
 7) SHEET A2.02 THE NEW SIDEWALKS ON THE BUILDING ARE
 5'-0" WIDE CODE COMPLIANT FOR AN ACCESSIBLE ENTRANCE AS
 DEPICTED IN FIGURE 404.2.4.1 (D) REQUIRING 60" BUT THE
 NEW SIDEWALK ON THE SIDE OF THE BUILDING IS ONLY 4'-0"
 WIDE A NEW NON-CODE COMPLIANT ELEMENT.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved