2013-04-23 17:28:08****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. OK
  
 2. PAPERWORK ATTACHED IS FOR 947 43RD ST. PLEASE
 PROVIDE CURRENT FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS FOR THE PRODUCTS INSTALLED FAC9N-3. PLEASE
 REVISE THE FLOOR PLAN TO INDICATE WHICH WINDOW PRODUCT
 WAS INSTALLED IN EACH LOCATION. A REVISION WAS ISSUED
 FOR THIS PERMIT, ADDING OTHER WINDOW PRODUCTS, BUT NOT
 CLEAR WHICH WERE INSTALLED AND AT WHAT LOCATION.
  
 2ND REVIEW, FLOOR PLAN NOT PROVIDED. INCLUDE ROOM
 DESIGNATIONS AND SIZES, WINDOW TYPE.
  
 CURRENT PRODUCT APPROVALS NOT PROVIDED.
  
 3. OK
  
 4. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM
 /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF)
  
 NOA PROVIDED, INSTALLATION SCHEDULE NOT PROVIDED.
  
 NEW COMMENT:
  
 SHOW EMERGENCY MEANS OF ESCAPE AND RESCUE ON THE FLOOR
 PLAN, FBC R 310.
  