Plan Review Notes
Plan Review Notes For Permit 12100638
Permit Number 12100638
Review Stop E
Sequence Number 1
Notes
Date Text
2012-10-26 08:56:2612100638
 709 11TH STREET
 ADD ELECTRIC METER TO SFD
  
 PROVIDE WIRE AND CONDUIT SIZE PROPOSED. NEC 310.15
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  