| Plan Review Notes For Permit 12100620 |
| Permit Number |
12100620 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-10-24 15:38:36 | PROVISO | | | REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS | | | 2010 FLORIDA ENERGY CODE. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|