Plan Review Notes
Plan Review Notes For Permit 12100614
Permit Number 12100614
Review Stop P
Sequence Number 1
Notes
Date Text
2012-11-19 14:28:48FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 THE EXTERIOR SINK IS NOT PERMITTED TO WET VENT THE
 BATHROOM GROUP. A LAV. STACK OR VERTICAL DRY VENT IS
 PERMITTED. (UPDATE 12/12/12 OWNER HAS IDENTIFIED THE
 EXTERIOR SINK AS A BAR SINK. THIS WOULD BE OK ON THE
 WET VENT)
 P3108.1 HORIZONTAL WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL ARE PERMITTED TO BE
 VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE
 CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND
 FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION
 OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM
 FIXTURE DRAIN CONNECTION. EACH FIXTURE DRAIN SHALL
 CONNECT HORIZONTALLY TO THE HORIZONTAL BRANCH BEING WET
 VENTED OR SHALL HAVE A DRY VENT. EACH WET-VENTED
 FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO THE
 HORIZONTAL WET VENT. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT.
 P3108.2.1 HORIZONTAL WET VENT. ...NOT MORE THAN ONE
 WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF
 THE DRY-VENTED FIXTURE DRAIN CONNECTION.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  