| Plan Review Notes For Permit 12100614 |
| Permit Number |
12100614 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-11-19 14:28:48 | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | THE EXTERIOR SINK IS NOT PERMITTED TO WET VENT THE | | | BATHROOM GROUP. A LAV. STACK OR VERTICAL DRY VENT IS | | | PERMITTED. (UPDATE 12/12/12 OWNER HAS IDENTIFIED THE | | | EXTERIOR SINK AS A BAR SINK. THIS WOULD BE OK ON THE | | | WET VENT) | | | P3108.1 HORIZONTAL WET VENT PERMITTED. | | | ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS | | | LOCATED ON THE SAME FLOOR LEVEL ARE PERMITTED TO BE | | | VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE | | | CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND | | | FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION | | | OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM | | | FIXTURE DRAIN CONNECTION. EACH FIXTURE DRAIN SHALL | | | CONNECT HORIZONTALLY TO THE HORIZONTAL BRANCH BEING WET | | | VENTED OR SHALL HAVE A DRY VENT. EACH WET-VENTED | | | FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO THE | | | HORIZONTAL WET VENT. ONLY THE FIXTURES WITHIN THE | | | BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED | | | HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL | | | DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT. | | | P3108.2.1 HORIZONTAL WET VENT. ...NOT MORE THAN ONE | | | WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF | | | THE DRY-VENTED FIXTURE DRAIN CONNECTION. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|