| Plan Review Notes For Permit 12100614 |
| Permit Number |
12100614 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-11-30 14:10:37 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT | | | SIZING CALCULATIONS AS REQUIRED BY FBCR M1401.3. | | | | | | 2) SUBMIT TWO SETS OF MECHANICAL PLANS THAT SPECIFY THE | | | DUCT SIZES, GRILL SIZES AND CFMS AT EACH SUPPLY. CITY | | | AMENDMENTS 107.3.5.3 | | | | | | 3) SPECIFY THE RETURN AIR GRILL AND DUCT SIZES ON THE | | | PLANS SHOWING COMPLIANCE WITH FBC M1602.4. | | | | | | 4) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS. SPECIFY | | | THE LOCATION OF THE EQUIPMENT AND THE SEER FOR THE | | | EQUIPMENT ON THE PLANS. CITY AMENDMENTS 107.3.5.3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|