Notes
Date Text
2012-11-30 14:10:372010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS AS REQUIRED BY FBCR M1401.3.
  
 2) SUBMIT TWO SETS OF MECHANICAL PLANS THAT SPECIFY THE
 DUCT SIZES, GRILL SIZES AND CFMS AT EACH SUPPLY. CITY
 AMENDMENTS 107.3.5.3
  
 3) SPECIFY THE RETURN AIR GRILL AND DUCT SIZES ON THE
 PLANS SHOWING COMPLIANCE WITH FBC M1602.4.
  
 4) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS. SPECIFY
 THE LOCATION OF THE EQUIPMENT AND THE SEER FOR THE
 EQUIPMENT ON THE PLANS. CITY AMENDMENTS 107.3.5.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW