| Notes |
| Date |
Text |
| 2012-10-31 10:16:39 | 12100609 | | | 5200 N. FLAGLER DRIVE # 1103 | | | APARTMENT REMODEL | | | | | | SCOPE OF ELECTRICAL WORK INSUFFICIENTLY DETAILED. | | | PLEASE PROVIDE THE FOLLOWING: | | | | | | INDICATE THE SIZE AND LOCATION OF THE ELECTRICAL PANEL. | | | ON A FLOOR PLAN SHOW THE LOCATION OF ALL NEW AND | | | EXISTING LIGHTING OUTLETS, RECEPTACLE OUTLETS AND SMOKE | | | DETECTORS. NEC 215.5 | | | VERIFY SMOKE ALARMS ARE PROVIDED INSIDE AND OUTSIDE ALL | | | SLEEPING AREAS. 2010 FBC R314, 315 | | | VERIFY THE KITCHEN COUNTER TOP RECEPTACLES AND BATHROOM | | | RECEPTACLES ARE GFCI PROTECTED. NEC 210.8 | | | INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER | | | RESISTANT. NEC 406.11 | | | ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE | | | PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC | | | 210.12 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|