| 2012-10-26 10:38:25 | 12100602 | | | 211 WESTMINSTER ROAD | | | PV SYSTEM | | | | | | INDICATE ON PLANS THE TYPE AND MATERIAL OF ALL REQUIRED | | | ELECTRICAL SAFETY SIGNS WITH SPECIFIC WORDING FOR EACH | | | REQUIRED LOCATION. SIGN MUST BE LEGIBLE, INDELIBLE, | | | PERMANENT AND SUITABLE FOR THE LOCATION AND | | | ENVIRONMENT. NEC 690.5 (C), 690.35(F), 690.70, 690.53, | | | 690.56, 705 10, 705.12(D)(7) | | | | | | PROVIDE A METAL ENCLOSURE FOR CONDUCTORS WITHIN THE | | | BUILDING. NEC 690.31(E) | | | | | | PROVIDE A GROUNDING DETAIL FOR THE SOLAR ARRAY AND | | | MOUNTING SYSTEM. NEC 690.43 | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|