Plan Review Notes
Plan Review Notes For Permit 12100555
Permit Number 12100555
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2013-03-18 11:40:591721 PALM BEACH LAKES BOULEVARD - 10 BUILDINGS IN MALL
 PERMIT #12100555
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REVIEW #1 COMMENT TO BE ELIMINATED:
 FIRE ALARM: FIRE ALARM NOTIFICATION SHALL BE
 ACCOMPLISHED WITH PRE-RECORDED VOICE ANNOUNCEMENTS FOR
 ALL MALL BUILDINGS. PROVIDE SPEAKER/STROBE APPLIANCES
 THROUGHOUT.
 (NOTE: THIS FIRE REVIEW COMMENT IS BEING RETRACTED DUE
 TO ADDITIONAL CODE RESEARCH, NFPA 101 INDICATES THAT
 VOICE ANNOUNCEMENTS SHALL BE PERMITTED (NOT REQUIRED).
  
  
 REVIEW #1 COMMENTS:
 SHEET C403 & C405: NO FIRE LANE CURBS OR SIGNS LOCATED
 ON PLAN FOR "H" BUILDINGS. INDICATE FIRE LANES ON BOTH
 FRONT AND REAR OF BUILDINGS.
  
 SHEET C602: FIRE HYDRANTS WILL NEED TO BE INSTALLED AND
 MAINTAINED WITH WORKING CLEARANCES OF 7'-6" TO THE
 FRONT/SIDES AND 4'-0" TO THE REAR. ANY PARKING SPACES
 LOCATED WITHIN THIS BUFFER ZONE WILL NEED TO BE
 INDICATED AS "NO PARKING" STALLS.
  
 SHEET C602: FIRE DEPARTMENT CONNECTION FOR FUTURE
 BUILDING "PBA #5" SHALL BE LOCATED WITHIN 150 FEET OF A
 FIRE HYDRANT.
  
 SHEET LS1: THE OCCUPANT LOAD FACTOR SHOULD BE 30 SQ.FT.
 PER PERSON (IN LIEU OF 50 SQ.FT. PERSON) FOR MERCANTILE
 OCCUPANCIES WITH SALES AREAS ON THE STREET LEVEL. THIS
 OCCUPANT LOAD FACTOR WILL RESULT IN A REVISED OCCUPANT
 LOAD OF 14,362 PERSONS FOR THE MERCANTILE OCCUPANCY AND
 AN OVERALL OCCUPANT LOAD OF 14,937 PERSONS.
  
 SHEET LS2 AND SEVERAL OTHER SHEETS: THE OCCUPANT LOAD
 FACTOR SHOULD BE 30 SQ.FT. PER PERSON (IN LIEU OF 50
 SQ.FT. PERSON) FOR MERCANTILE OCCUPANCIES WITH SALES
 AREAS ON THE STREET LEVEL.
  
 SHEET LS2 AND SEVERAL OTHER SHEETS: IN BUILDINGS
 PROTECTED THROUGOUT BY AN AUTOMATIC SPRINKLER SYSTEM,
 DEAD-END CORRIDORS FOR BOTH MERCANTILE AND STORAGE
 OCCUPANCIES SHALL NOT EXCEED 20 FEET PER SECTION
 36.2.5.2.1 AND SECTION 42.2.5 (NFPA 101 - W/ FLORIDA
 AMENDMENTS).
  
 SHEET LS2 AND SEVERAL OTHER SHEETS: STENCIL/PAINT REAR
 EXIT DOORS, "EXIT DOOR - DO NOT BLOCK."
  
 SHEET LS7: PROVIDE ADDITIONAL EXIT SIGNS IN LONG
 CORRIDORS. PER SECTION 7.10.1.5.2 (NFPA 101), SIGNS
 SHALL BE PLACED SUCH THAT NO POINT IN A CORRIDOR IS IN
 EXCESS OF THE RATED VIEWING DISTANCE OR 100 FEET,
 WHICHEVER IS LESS, FROM THE NEAREST SIGN.
  
 SHEET LS7: PROVIDE ADDITIONAL EXIT SIGN NEAR ASSEMBLY
 OCCUPANCY BATHROOMS.
  
 SHEET A507: FOR ASSEMBLY OCCUPANCIES (FOOD COURT) WITH
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS, PANIC HARDWARE
 SHALL BE PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH.
 NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT
 BE RELEASED BY THE PANIC HARDWARE.
  
 DOOR SCHEDULES: ANY DOORS FEATURING A THUMB-TURN STYLE
 LOCK SHALL ALSO BE EQUIPPED WITH A READILY
 DISTINGUISHABLE LOCK/UNLOCK INDICATOR.
  
 WALL DETAILS: EACH FIRE-RATED BARRIER SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 WALL DETAILS: ALL EXIT ACCESS CORRIDORS AND EXIT
 PASSAGEWAYS SHALL HAVE SIGNS OR STENCILING READING
 "EXIT CORRIDOR - NO STORAGE PERMITTED." CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730