| Plan Review Notes For Permit 12100555 |
| Permit Number |
12100555 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-02-11 10:38:49 | ***PROVISO*** | | | 1. MINIMUM SIZE IN ANY DIRECTION FOR SCUPPERS IS 4" | | | 1107.3 SIZING OF SECONDARY DRAINS. | | | ...SCUPPERS SHALL NOT HAVE AN OPENING DIMENSION OF LESS | | | THAN 4 INCHES (102 MM). THE FLOW THROUGH THE PRIMARY | | | SYSTEM SHALL NOT BE CONSIDERED WHEN SIZING THE | | | SECONDARY ROOF DRAIN SYSTEM. | | | | | | 2. SHEET A403 & A404 - ONE AMBULATORY STALL IS REQUIRED | | | IN EACH RESTROOM WITH 6 OR MORE WATER CLOSETS/ URINALS. | | | 213.3.1 TOILET COMPARTMENTS. | | | WHERE TOILET COMPARTMENTS ARE PROVIDED, AT LEAST ONE | | | TOILET COMPARTMENT SHALL COMPLY WITH 604.8.1. IN | | | ADDITION TO THE COMPARTMENT REQUIRED TO COMPLY WITH | | | 604.8.1, AT LEAST ONE COMPARTMENT SHALL COMPLY WITH | | | 604.8.2 WHERE SIX OR MORE TOILET COMPARTMENTS ARE | | | PROVIDED, OR WHERE THE COMBINATION OF URINALS AND WATER | | | CLOSETS TOTALS SIX OR MORE FIXTURES. | | | |
|