| Plan Review Notes For Permit 12100555 |
| Permit Number |
12100555 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-02-15 13:21:57 | MECHANICAL PLANS DENIED | | | 1) PROVIDE DUCT SIZE FOR ALL DUCT | | | SUPPLY RETURN AIR AND EXHAUST, TRANSFER DUCT. | | | IN BUILDING # 10 PER SECTION 107 FBC 2010 | | | 2) PROVIDE IDENTIFICATION FOR ALL RTU UNITS ON THE ROOF | | | PER SECTION 304.12 AREA SERVED 2010 FBC (M) | | | 3) PAGE M221 OF THE PLANS REFER TO SECTION 304.11 | | | GUARDS AND | | | 501.2.1 LOCATION OF EXHAUST OUTLETS. 2010 FBC (M) | | | 4) PAGE M501 OF THE PLANS PROVIDE THE BOLT SIZE | | | THROUGH THE ROOF ON THE PIPE SUPPORT DETAIL. | | | PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M) | | | 5) PAGE 502 PROVIDE A DETAIL SHOWING | | | CURB TO ROOF AND RTU TO CURB TIEDOWN (PROVIDE | | | BOLT SIZE ON DETAIL) | | | PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M) | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] | | | | | | | | | |
|