2013-02-15 13:21:57MECHANICAL PLANS DENIED
 1) PROVIDE DUCT SIZE FOR ALL DUCT
 SUPPLY RETURN AIR AND EXHAUST, TRANSFER DUCT.
 IN BUILDING # 10 PER SECTION 107 FBC 2010
 2) PROVIDE IDENTIFICATION FOR ALL RTU UNITS ON THE ROOF
 PER SECTION 304.12 AREA SERVED 2010 FBC (M)
 3) PAGE M221 OF THE PLANS REFER TO SECTION 304.11
 GUARDS AND
 501.2.1 LOCATION OF EXHAUST OUTLETS. 2010 FBC (M)
 4) PAGE M501 OF THE PLANS PROVIDE THE BOLT SIZE
 THROUGH THE ROOF ON THE PIPE SUPPORT DETAIL.
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 5) PAGE 502 PROVIDE A DETAIL SHOWING
 CURB TO ROOF AND RTU TO CURB TIEDOWN (PROVIDE
 BOLT SIZE ON DETAIL)
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)