| Plan Review Notes For Permit 12100509 |
| Permit Number |
12100509 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-10-17 13:47:21 | RESIDENTIAL (R3) REROOF BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC-RESIDENTIAL. | | | | | | 1- SHINGLES ON A 3/12 PITCH REQUIRES 2 LAYERS OF | | | UNDERLAYMENT. SEC. R905.2.2. IF CONTRACTOR IS PROPOSING | | | TO USE SELF-ADHERING UNDERLAYMENT APPLIED DIRECT TO THE | | | DECK, THEN, REQUEST FOR APPROVAL FOR THIS METHOD NEEDS | | | TO BE SUBMITTED FOR THE BUILDING OFFICIAL APPROVAL | | | UNDER ALTERNATIVE MATERIALS, DESIGN AND METHODS OF | | | CONSTRUCTION SEC. 104.11 CITY AMENDMENTS TO FBC. | | | | | | 2- FLAT ROOF NOA SUBMITTED: CLEARLY IDENTIFY WHICH | | | APPROVED ASSEMBLY IS GOING TO BE INSTALLED. SEC. | | | 107.2.1.2 CITY AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|