2012-10-23 10:14:0412100505
 4100 WASHINGTON ROAD
 SFD ELECTRICAL REVISION
  
  
 THE FOLLOWING CODE REQUIREMENTS WERE NOTED ON THE PLAN.
  
 PROVISO:
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 THE NEW BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS.
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
 THE BATHROOMS REQUIRE A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  
  