| Plan Review Notes For Permit 12100482 |
| Permit Number |
12100482 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-12-10 08:44:24 | *** MECHANICAL PLAN CORRECTIONS AS NOTED IN LAST PLAN | | | REVIEW 11/30/12 *** | | | | | | 1) EQUIPMENT SCHEDULE ON MECHANICAL PLAN A-3 DOES NOT | | | COINCIDE WITH THE COOLING LOAD CAL'S OR E-CAL'S.. | | | PLEASE CORRECT PER 2010 FBC/RES. N1101, RES M1401.3 AND | | | FBC/ENERGY 403.6.1, ENERGY 503.2.2. | | | | | | 2) ENERGY CAL'S. NEED TO BE SIGNED & DATED BY THE | | | OWNER/AGENT, PER 2010 FBC/ENERGY 103.2.3.2. | | | | | | 3) RETURN AIR TRANSFER GRILLS TO THE TWO SMALL BEDROOMS | | | ARE UNDER SIZED. PLEASE CORRECT PER 2010 FBC/M 601.4. | | | TRANSFER GRILL AREA SHALL BE 50 SQ. IN. PER 100CFM'S OF | | | SUPPLY AIR. | | | | | | 4) CLOTHES DRYER VENT IS DISCHARGING TO CLOSE TO THE | | | A/C CONDENSER UNIT, LINT MAY BE SUCKED INTO CONDENSER | | | COIL. PLEASE SEE 2010 FBC/M 501.2. | | | | | | *** MECH. PLAN REVIEW BY TOM GORDON (HY-BYRD, INC.) | | | *** FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710 |
|