2012-12-10 08:44:24*** MECHANICAL PLAN CORRECTIONS AS NOTED IN LAST PLAN
 REVIEW 11/30/12 ***
  
 1) EQUIPMENT SCHEDULE ON MECHANICAL PLAN A-3 DOES NOT
 COINCIDE WITH THE COOLING LOAD CAL'S OR E-CAL'S..
 PLEASE CORRECT PER 2010 FBC/RES. N1101, RES M1401.3 AND
 FBC/ENERGY 403.6.1, ENERGY 503.2.2.
  
 2) ENERGY CAL'S. NEED TO BE SIGNED & DATED BY THE
 OWNER/AGENT, PER 2010 FBC/ENERGY 103.2.3.2.
  
 3) RETURN AIR TRANSFER GRILLS TO THE TWO SMALL BEDROOMS
 ARE UNDER SIZED. PLEASE CORRECT PER 2010 FBC/M 601.4.
 TRANSFER GRILL AREA SHALL BE 50 SQ. IN. PER 100CFM'S OF
 SUPPLY AIR.
  
 4) CLOTHES DRYER VENT IS DISCHARGING TO CLOSE TO THE
 A/C CONDENSER UNIT, LINT MAY BE SUCKED INTO CONDENSER
 COIL. PLEASE SEE 2010 FBC/M 501.2.
  