Plan Review Notes
Plan Review Notes For Permit 12100482
Permit Number 12100482
Review Stop E
Sequence Number 2
Notes
Date Text
2012-12-21 15:01:01PLEASE REVISE THE PLANS TO INCLUDE THE REQUIREMENTS
 NOTED ON THE PREVIOUS REVIEW AND LISTED HERE.
  
  
 12100482
 500 HURON PL.
 SFD
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE
 PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC
 210.12
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. 2010 FBC R314, 315
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
 MINIMUM SIZE SERVICE CONDUCTORS FOR A 200 AMPERE
 RESIDENTIAL SERVICE IS 2/0 COPPER. NEC 310.16
 THE ELECTRICAL SERVICE REQUIRES A MAIN 200 AMPERE
 SERVICE DISCONNECT OUTSIDE ADJACENT TO THE METER. NEC
 230.70
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  
  