| Notes |
| Date |
Text |
| 2012-11-09 11:33:46 | 12100482 | | | 500 HURON PL. | | | SFD | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE | | | PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC | | | 210.12 | | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | | OF EACH ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND. NEC 250.94 | | | MINIMUM SIZE SERVICE CONDUCTORS FOR A 200 AMPERE | | | RESIDENTIAL SERVICE IS 2/0 COPPER. NEC 310.16 | | | THE ELECTRICAL SERVICE REQUIRES A MAIN 200 AMPERE | | | SERVICE DISCONNECT OUTSIDE ADJACENT TO THE METER. NEC | | | 230.70 | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|