Date Text
2012-12-28 16:21:34****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 SEE FBC R 310, FBC 2010 EXISTING BUILDING 604.1.
  
 1. THE 50" HIGH WINDOW IS NOT OF SUFFICIENT HEIGHT FOR
 EMERGENCY ESCAPE AND RESCUE. PHOTOGRAPHS FROM APRIL
 2011 SHOW AWNING WINDOWS. AS AWNING WINDOWS PROVIDE A
 REMOVABLE PANEL, CLEAR OPENING PREVIOUSLY EXCEEDED THE
 REQUIREMENT OF 24". THE NEW SINGLE HUNG WINDOW FOR
 BEDROOM #4, INSTALLED SOMETIME AFTER APRIL 2011, AT 17"
 CLEAR OPENING HEIGHT DOES NOT MEET THE EMERGENCY ESCAPE
 AND RESCUE REQUIREMENT.
  
 2. VALUE IS TO INCLUDE ALL MATERIALS AND VALUE OF
 LABOR, FBC 109.3.
  
 PROVIDE A COPY OF THE RECEIPT FOR MATERIALS.
  