Plan Review Notes
Plan Review Notes For Permit 12100434
Permit Number 12100434
Review Stop P
Sequence Number 2
Notes
Date Text
2012-11-09 10:35:01****PROVISO****
  
 THE DRINKING FOUNTAIN SPECIFIED ON P-1 (ELKAY EZ4) DOES
 NOT COMPLY WITH FBC ACCESSIBILITY 2010 211.2 NO FEWER
 THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED:
  
 THE DRINKING FOUNTAIN IS REQUIRED TO BE HI/LOW TYPE OR
 THE EXCEPTION:
 FBC ACCESSIBILITY 2010 211.2 MINIMUM NUMBER. NO FEWER
 THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6
 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  